Prime Rating at rated rpm ( as per ISO8528)1
kVA
125
kW

100
Genset Model
KG1-125WS
Frequency
Hz
50
Power factor
lagging
0.8
Voltage
V
415 3Ø
Governing class ( As per ISO 8528 Part-V)
G3
Noise level
dBA
< 75
Fuel Consumption* At 100 % Load
Ltrs/Hr
27.4
At 75 % Load
20.2
At 50 % Load
15.3
Fuel Tank Capacity
Ltrs
230
Overall dimensions of genset (L x W x H)^

mm
3240 x1340 x1795
Dry weight of genset with canopy (approx..)^
Kg
2000
Wet weight of genset with canopy (approx..)^
Kg
2400
Electrical Battery starting voltage
Volts-DC
12
ENGINE
Engine Model
4K1080TA G2
Rated output (Prime Continuous rating as per ISO 8528-1)
kW
114.7
HP
156
No. of cylinder
Number
4
Cubic capacity 2
Ltrs
4.32
Bore x Stroke
mm
105x125
Rated Speed
RPM
1500
Aspiration
NA/TC/TA
TA
Lube Oil change period
hrs.
500
Lube oil Sump Capacity
Ltrs
14.0
Coolant Capacity
Ltrs
21.0
ALTERNATOR
Insulation Class
Class H
Alternator Efficiency (at 100% load) 0.8 pf**
%
92.6
Max Voltage Dip at Full Load 0.8 pf Lag
sec
< 20 %
Max Time to build up rated voltage at Rated RPM < 5 sec provided engine reach the rated speed
For intermediate ratings, kindly contact nearest KOEL office Notes ^ Tolerances Apply *With 0.845 Specific Gravity of diesel ( 5 % Tolerance )
** Efficiency of Alternator as per standards IS 4722 and IEC 34-1 For Site Conditions other than standard operating conditions consult KOEL for available prime power.

Prime rating and Stand‐by rating1

‘Prime power’ is designed for Unlimited hours, as compared to 'Emergency stand-by' designed for 200 hours in a year. Prime rated Gensets also permit 10% temporary overloading. Users need to carefully select the Genset rating to meet their requirement. KOEL offers Prime power as standard offer. Contact KOEL for stand-by ratings.

Engine capacity does matter2

Engine capacity (cc) plays a vital role in Genset performance. Higher engine capacity leads to a robust and stable Genset performance.Higher engine capacity also enables Genset to respond quickly & positively to sudden load additions.

1.Canopy

  • Ease of Access and Serviceability
  • Aesthetically designed, weather and sound resistant enclosure
  • Insulation conforms to UL94-HF1 class for flammability

2.Controller

  • Microprocessor based fully configured
  • Graphical bigger LCD display
  • Best in class monitoring and diagnostic
  • Integrable with AMF

3.Engine

  • O2E Series: Low emission, high efficiency engines
  • Compact, Robust and Rugged Design
  • 500 hours lube-oil change period

4.Alternator

  • Best In Class Efficiency
  • Special Windings to Reduce Harmonics
  • Vacuum Pressure Impregnation and epoxy gel coating on winding

Monitoring Features

  • Phase Voltages, Phase Currents, kVA, KW, KVAr, KWH, Power Factor
  • Lube oil Pressure, Engine Temperature, RPM, Run Hours, Number of starts, Fuel Level, Auto / Manual Stop
  • Battery charge condition
  • Common Alarm / Hooter output, AMF feature with ATS

Optional Features

  • Modbus communication

Diagnostic Features

Battery charging failure, Over speed, Under speed, Over Current, Under Voltage, Over Voltage, Over KW, Phase Sequence monitoring, Phase missing, Common Alarm, Hooter output

Low lube oil Pressure, High Engine Temperature, Low/High battery voltage, Low Fuel Level alarm, Over Crank protection, Routine Maintenance indicator, Genset Test Facility, fail to start/stop. Being in control of your Genset is certainly a winning edge!